Home>AS Standards>AS 7240.12:2018 pdf free

AS 7240.12:2018 pdf free

AS 7240.12:2018 pdf free.Fire detection and alarm systems
The program necessary to comply with this part of ISO 7240 and any preset data, such as manufacturer’s settings, shall be held in non-volatile memory. Writing to areas of memory containing this program and data shall be possible only by the use of some special tool or code and shall not be possible during normal operation of the detector.Site-specific data shall be held in memory which will retain data for at least two weeks without external power to the detector, unless provision is made for the automatic renewal of such data, following loss of power, within 1 h of power being restored.
Mount the specimen by its normal means of attachment in accordance with the manufacturer’s instructions. If these instructions describe more than one method of mounting, then the method considered to be most unfavourable for each test shall be chosen.If a test method requires a specimen to be operational, then connect the specimen to suitable supply and monitoring equipment having the characteristics required by the manufacturer’s data. Unless otherwise specified in the test method, set the supply parameters applied to the specimen within the manufacturer’s specified range(s) and maintain them substantially constant throughout the tests. The value chosen for each parameter shall normally be the nominal value, or the mean of the specified range.
If a test procedure requires a specimen to be monitored to detect any alarm or fault signals, then connect the specimen to any necessary ancillary devices (e.g. through wiring to an end-of-line device for non-addressable detectors) to allow a fault signal to be recognized.
The specimens submitted shall be representative of the manufacturer’s normal production with regard to their construction and calibration. This implies that the mean response threshold value of the seven specimens found in the reproducibility test should also represent the production mean, and that the limits specified in the reproducibility test should also be applicable to the manufacturer’s production.AS 7240.12 pdf free download.

Related standards